The City of Phoenix is one of the few places that writes a pump-out schedule into its city code. Its June 2024 manual for food service establishments says a full cleaning is required once fats, oils, grease, and solids take up more than 25% of an interceptor, sets a 30-day cycle for indoor grease traps with a 90-day ceiling, and sets a not-less-than-every-3-months cycle for outdoor gravity interceptors. These are Phoenix rules under Phoenix City Code Chapter 28. They are not federal law, and they are not the rule in any other city.

Who issued the rules, and which version we read

The main source is Fats, Oils and Greases (FOG) Best Management Practices for Food Service Establishments, from the City of Phoenix Water Services Department, Environmental Services Division. The cover is dated June 2024. On November 22, 2026 it was still the “FOG Best Management Practices” file linked from the city’s Water Services “Documents and Annual Reports” page. The manual says it “should be used in conjunction with Chapter 28 and City of Phoenix Amended Uniform and International Plumbing Codes.”

Because a 2024 manual can fall behind the code, we also read the current text of Phoenix City Code § 28-15 (Interceptors—Maintenance) on the city’s official code host. That host said the code was “current through Ordinance G-7524, passed June 17, 2026.” The pump-out numbers match. Where the code says more than the manual does, we note it below.

Which interceptor you have decides your schedule

The manual describes two accepted types:

The 25% rule, as Phoenix words it

From the manual’s “Maintenance of Grease Interceptors” section:

Most types of interceptors stop working effectively when fats, oils, and solids reach 25% of the device’s capacity. If the FOG and solids occupy greater than 25% of the interceptor’s capacity, the FSE is required to perform a full cleaning of the interceptor. Cleaning must be performed by a licensed pumper.

The city code is more specific for gravity interceptors. Section 28-15(B) says the 25% limit is measured against “the total liquid volume capacity as measured at the static water level of the interceptor,” and counts “combined grease, lint, oil, sand, sludge, and solids accumulation.”

Pump-out intervals

DeviceWhat Phoenix requiresWhere it is written
Hydromechanical interceptor (grease trap)“Fully pumped out and cleaned every 30 days unless granted a variance by the Director. No hydromechanical interceptor may be allowed to go more than 90 days without maintenance.”Manual p. 3; PCC § 28-15(D)
Gravity interceptor at a food service establishment that captures FOGFull pump-out and cleaning “at a frequency of not less than once every 3 months unless granted a variance by the Director.”Manual p. 3; PCC § 28-15(C)
Gravity interceptor, other users (not the food-service case above)Pump often enough that accumulation stays at or under 25%, and “at least once every 12 months unless granted a variance by the Director.”PCC § 28-15(B) only. The food-service manual does not mention this.

The intervals are minimums, not targets. The manual says a new facility “should monitor the interceptor with the help of their pumping company or an Environmental Services Inspector and adjust the frequency to the actual amount of FOG accumulated,” and that “the interceptor may need to be pumped more frequently.” A variance can only come from the Director. The manual does not explain how to apply for one, so ask the Environmental Services Division.

What a proper pump-out looks like

Enzymes, bacteria, and solvents are prohibited

The manual says: “The use of chemicals, enzymes, proteins, bacteria, grease solvents, or emulsifiers to temporarily dissolve fats, oils, and grease is prohibited.” Code § 28-15(G) bans the same list, plus “other similar substances,” used “to dissolve FOG in lieu of physical cleaning.” If a vendor offers an additive in place of pumping, that does not satisfy the Phoenix schedule.

Records: three years, on site

The manual says: “All records documenting maintenance activities, including invoices provided by third-party service contractors, need to be available on site for three years per PCC Chapter 28.” It also says maintenance is “the sole responsibility of the user, or in the case of multiple user interceptors, the property owner.”

The code goes further on what each record should show. Section 28-15(F) requires records of “all cleaning, volume of waste removed, device capacity, waste disposal, repair, replacement, and maintenance required to demonstrate compliance.” The manual does not list those fields. Make sure each pumping invoice shows the gallons removed and where the waste went.

What inspectors check

The manual says Phoenix commercial inspections “are unannounced” and that inspectors “try to come in off hours.” They “will be in uniform, have City of Phoenix issued identification, and drive a City of Phoenix vehicle.” During an inspection, the inspector will want to see the following:

If something needs fixing, the inspector sets a deadline. The manual says “Extensions can be granted based on business needs if the request is in writing.”

A practical checklist for Phoenix operators

Every item below restates one of the rules quoted above. None of it is new.

  1. Find out which device you have. An indoor trap is on the 30-day / 90-day-maximum schedule. An outdoor gravity interceptor at a food service establishment is on the at-least-every-3-months schedule.
  2. If your inspector or pumper sees FOG and solids above 25% before the calendar date, pump early. The 25% rule applies either way.
  3. Hire a licensed pumper, watch the job, and confirm the unit is left completely empty with nothing poured back in.
  4. Keep every invoice on site for three years. Each one should show the volume removed, the device capacity, and where the waste was disposed.
  5. Do not use enzymes, bacteria, or solvents in place of pumping.
  6. Have a variance or extension? Keep the written approval with your records. The manual says extensions are requested in writing.

What the Phoenix manual does not give you

It does not name any pumpers or publish a hauler roster. It says cleaning “must be performed by a licensed pumper,” but it does not say which license or where to look one up. It does not list fees or variance criteria. Appendix B still carries a COVID-era note that over-the-counter plan reviews are “by appointment only,” with 602-534-6502 as the number. That note may be out of date, so confirm with the city before you rely on it. For questions, the manual’s back cover lists the Environmental Services Division at 2474 South 22nd Avenue, Building 31, Phoenix, Arizona 85009, (602) 262-1859, phoenix.gov/esd.

Why this matters outside Phoenix

Many agencies give no number at all. Vallejo’s restaurant brochure, for example, says to clean traps “frequently” and on “a regular basis.” Phoenix’s numbers are a useful example of what a written schedule looks like, but they do not carry over to other cities. Federal pretreatment rules (40 CFR 403.5, which the manual cites) ban discharges that obstruct sewer flow. The manual does not point to any federal pump-out interval, and neither do we. Check your own sewer agency’s ordinance.

Sources

  1. City of Phoenix Water Services Department, Environmental Services Division, Fats, Oils and Greases (FOG) Best Management Practices for Food Service Establishments, June 2024 (15-page PDF), https://www.phoenix.gov/content/dam/phoenix/waterservicessite/documents/FOG_BMP_Manual_2024_06.pdf. Downloaded and checked November 22, 2026, Pacific Time.